Details
Sonel S-25 DC High Voltage Insulation Tester
Index: WMGBS25DC
Description
Index: WMGBS25DC
Description
MV and HV insulation under full control
The S-25 DC device is universal high voltage tester. Capacitive loads, such as shielded power cables, will be properly and automatically discharged in case of an error or at the end of testing time by the integrated discharge device
Key switch, switch-on interlock and a protective ground circuit ensure maximum safety.
S-25 DC stands out in particular. Not just with modest dimensions. Thanks to an internal rechargeable battery it enables mains-independent testing.
Sonel offers online training course on the use of this product (instructional video and consultation with a specialist).
Features
- Easy operation
- Robust construction, low weight
- Integrated timer:
- max. 30 min
- Discharge device:
- integrated
- Internal battery charger with deep discharge protection
- Voltage measurement direct at HV output
- Short-circuit-proof output:
- electronically limited output current
- Protective ground connection
- Mains-independent by internal rechargeable battery
Fields of application
- Testing at recommissioning of cable systems after maintenance and repair
- Testing of newly installed cables an cable joints before commissioning
- Voltage testing at cable sheath
- Testing of electrical equipment
Technical Specification
S-25 DC | S-50 DC | S-80 DC | S-110 DC | S-120 DC | |
---|---|---|---|---|---|
Power supply | • internal rechargeable battery • mains, switchable 115 / 230 V, 50-60 Hz • external DC voltage source | mains 230 V / 50 Hz (optional: 115 V / 60 Hz | mains 230 V / 50 Hz (optional: 115 V / 60 Hz | mains 230 V / 50 Hz (optional: 115 V / 60 Hz | mains 230 V / 50 Hz (optional: 115 V / 60 Hz |
Power consumption | max. 120 VA | max. 900 VA | max. 900 VA | max. 900 VA | max. 900 VA |
Output voltage | • 0…25 kV DC • infinitely adjustable • negative polarity • ripple < 0,25% | • 0…50 kV DC • infinitely adjustable • negative polarity | • 0…80 kV DC • infinitely adjustable • negative polarity | • 0…110 kV DC • infinitely adjustable • negative polarity | • 0…120 kV DC • infinitely adjustable • negative polarity |
Rated output current at max. output voltage | 1.5 mA electronically limited | 6 mA | 5 mA | 4 mA | 3,5 mA |
Battery operation at full load | 45 min | - | - | - | - |
Discharge - integrated automatic discharge device | 3000 J 9.6 µF at 25 kV | 7500 J 6 µF at 50 kV | 12 250 J 4 µF at 75 kV 3.5 µF at 80 kV | 15 000 J 3 µF at 100 kV 2.5 µF at 110 kV | 18 750 J 2.4 µF at 125 kV 2.6 µF at 120 kV |
Voltage measuring range | 0…30 kV | 0…50 kV | 0…80 kV | 0…110 kV | 0…130 kV |
Current measuring ranges | 0…200 µA / 0…2 mA manual or automatic switching between ranges | 0…100 μA / 1 mA / 10 mA manual switching between ranges | 0…100 μA / 1 mA / 10 mA manual switching between ranges | 0…100 μA / 1 mA / 10 mA manual switching between ranges | 0…100 μA / 1 mA / 10 mA manual switching between ranges |
Operating temperature | -25…+55°C -13…+131°F |
-25…+55°C -13…+131°F |
-25…+55°C -13…+131°F |
-25…+55°C -13…+131°F |
-25…+55°C -13…+131°F |
Storage temperature | -40…+70°C -40…+158°F |
-40…+70°C -40…+158°F |
-40…+70°C -40…+158°F |
-40…+70°C -40…+158°F |
-40…+70°C -40…+158°F |
View more about Sonel S-25 DC High Voltage Insulation Tester on main site